300 kW generator 480 volt w/ 600-amp breaker...2-sets of 4/0 wire I have a project to install a 480 volt, 250/500 kW UPS between the transfer switch and the 600-amp MDP. The problem I found is the wiring from the 600-amp 100% rated GE breaker Spectra ...
Started by mallard duck on
, 10 posts
by 6 people.
Answer Snippets (Read the full thread at mikeholt):
This generator....
1 THHN wire in 1-1/2" conduit on the 225-amp.
Saw no.
Between the 300 kW generator's 600-amp breaker as the generator was only put in a couple years back.
At the switchgear is feeding the ATS with 2 sets of 4/0 .
|
|
I'd like to sell this thing. I bought it from local small town fire dept. It was running but radiator and oil lines were in tough shape. I replaced those and rebuilt the governor which was leaking. It still needs a little work to fully refurb but I have...
Started by balwit on
, 2 posts
by 2 people.
Answer Snippets (Read the full thread at smokstak):
If you still have the generator call me 314 808 0054 thanks mitch.
|
|
Trying to restore a Military Generator PU-286/G powered by a four cylinder Hercules ZXB flat head engine. This is a water cooled 5 KW generator with a squirrel cage blower and small radiator at the top of the cage. Need the water intake hose adapter that...
Started by Don Smith on
, 20 posts
by 5 people.
Answer Snippets (Read the full thread at smokstak):
This is a water cooled 5 KW generator with a squirrel cage powered by a four cylinder Hercules....
This is a water cooled 5 KW generator cylinder Hercules ZXB flat head engine.
By a four cylinder Hercules ZXB flat head engine.
|
Ask your Facebook Friends
|
I'll tell the whole story soon . For now, the generator I obtained was my uncle who has recently passed away. Waukesha four cylinder gas engine, model FC 140 E,
Number, 625558, .. The generator is a kohler, model 10M61H3, number 99123,
115-230 volts, ...
Started by advance9572 on
, 20 posts
by 5 people.
Answer Snippets (Read the full thread at smokstak):
Steve was the gentleman that really into the wall, but its a meter that ... .
Those people were great.
It took two hours to take it off the replacement brushes for the generator .
That excites the generator was rusted in the closed position.
|
|
Standby generator Im thinking about getting a whole house/standby generator and looking to get some info on what I should expect to pay for installation. I understand that every install is different, just looking for some ballpark figures...thanks
Started by fng on
, 20 posts
by 13 people.
Answer Snippets (Read the full thread at bayoushooter):
The 18 kw will not start up with bot units running.
I have a 4 ton and 3 ton central air compressor for cooling .
I wound up buying the Kohler 18 kw Residential installed
was $7000.00.
Generator I did a lot of research a year ago.
|
|
I recently acquired a Generac 25KW Model Number 00609-4 S/N 3048955 standby generator with 285 hours on it and it appears to be manufactured in the early 90s but not sure._ Engine valve cover says TOFAS, block has 91 on it, and a Generac tag that says...
Started by Bdgriner on
, 19 posts
by 8 people.
Answer Snippets (Read the full thread at smokstak):
I think that set is a 3600RPM 4 cylinder, if so the most relevant advice I have about maintenance is that you will probably spend more time working on it than you will actually using... .
There is a good chance that the engine was made under license from Fiat .
|
|
I recently bought/practically stole, this generator and would like to have a schematic for it as there is none so far to be found. I found info and downloaded a manual and parts list for the engine no problem but so far nothing on the generator In fact...
Started by madokie on
, 12 posts
by 4 people.
Answer Snippets (Read the full thread at smokstak):
I could send you TP-1184 for the ....
I have only found 5.5 and 7 KW RV units using the two cylinder engine but they used the K582 engine.
The motor on mine is a K482.
I downloaded a schematic for the 5ckm21 but its not the same generator.
|
|
This is a thread starter for the purpose of building a F.A.Q. page (frequently asked questions) on Generators and stand-by power. This thread will be edited and maintained as a F.A.Q. (Do not drift off topic.) Moderators will also edit posts in this thread...
Started by Harry on
, 20 posts
by 9 people.
Answer Snippets (Read the full thread at smokstak):
kW or watts or real power ....
On a DC generator (unless it's exactly the same as the kW value, because DC equipment always has a PF rating applies because, amps or current is what causes the heating in the generator windings.
|
|
I got this generator years ago THe previous owner kindly remover ALL the ID info I would like to get some spare parts and a manual but need to to know what model it is
Thanks for your help
Dave
Started by Dmichels on
, 20 posts
by 10 people.
Answer Snippets (Read the full thread at smokstak):
B&p,
I agree with you that the base engine and generator look like the ones on my MEP-015, nothing else is familiar model generator it is ad get a....
Engine is rated at 3.0HP and generator at 1.5KW.
Air filter not paper air filter].
|
|
All,
I wanted to get everyones input/opinion.
If you were charged with writing the specifications for a new backup generator (roughly 20 KW, load calc already done).
What would you reccomend?
Obviously Propane or Natural gas is the best fuel choice (We...
Started by richard.bessey on
, 16 posts
by 11 people.
Answer Snippets (Read the full thread at smokstak):
They are out there and are very Kohler looking at new stuff, and spec a 4 pole generator end so you get a nice 1800 rpm unit, just them, for example it seems "fast....
In the 20 kw range I would look for a Onan 20 ES series generator.
|